Copper RHH/RHW-2/USE-2 600V 90°C XLPE Insulation Wire Cable
Copper RHH/RHW-2/USE-2 600V 90°C XLPE Insulation Cable
Application:
USE-2 cables are primarily used for power distribution, in raceways in accordance with National Electrical Code, except that the cable is not rated for use in cable tray. USE-2 is approved for direct burial and for service entrance below ground. USE-2 cables may be used in wet or dry locations, with ambient temperatures not exceeding 90°C. Voltage rating for USE-2 cable is 600V. Sizes 1/0 and larger rated for use in cable tray.
Conductors:
USE-2 conductor is a soft drawn bare copper with Class B stranding per ASTM.
Insulation:
USE-2 has abrasion, heat and moisture resistant cross-linked polyethylene insulation XLPE.
Standards:
UL standard 44
Requirements of the National Electrical Code
ASTM standards B 800, B 801
Federal Specification J – C – 30B
Sunlight resistant
Part Number |
Size AWG |
No.of strands |
Insulation Thickness (mils) |
Overall Diameter (inches) |
Weight Ibs./mft |
CU-USE-14 | 14* | 7 | 45 | 0.170 | 22 |
CU-USE-12 | 12 | 7 | 45 | 0.190 | 32 |
CU-USE-10 | 10 | 7 | 45 | 0.210 | 47 |
CU-USE-8 | 8 | 7 | 60 | 0.270 | 71 |
CU-USE-6 | 6 | 7 | 60 | 0.370 | 105 |
CU-USE-4 | 4 | 7 | 60 | 0.360 | 155 |
CU-USE-2 | 2 | 7 | 60 | 0.420 | 240 |
CU-USE-1 | 1 | 19 | 80 | 0.490 | 310 |
CU-USE-1/0 | 1/0 | 19 | 80 | 0.530 | 380 |
CU-USE-2/0 | 2/0 | 19 | 80 | 0.580 | 470 |
CU-USE-3/0 | 3/0 | 19 | 80 | 0.630 | 585 |
CU-USE-4/0 | 4/0 | 19 | 80 | 0.690 | 730 |
CU-USE-250 | 250 | 37 | 95 | 0.760 | 870 |
CU-USE-350 | 350 | 37 | 95 | 0.860 | 1190 |
CU-USE-500 | 500 | 37 | 95 | 0.990 | 1670 |
CU-USE-750 | 750 | 61 | 110 | 12.000 | 2500 |
CU-USE-1000 | 1000 | 61 | 110 | 1.350 | 3290 |
All values are nominal and subject to correction.
* #14 AWG not Type USE, Minimum UL Size for Type USE is 12 AWG.